28

Fault

Code

Bus fault

05

Inverter fault

06

Overload fault

07

Over temperature fault

08

Inverter short

14

Bus short

28

If the UPS system does not operate correctly, please attempt to solve the

problem using the table below.

Problem

Possible cause

Remedy

No indication, no
warning tone even
though system is
connected to mains
power supply

No input voltage

Check building wiring
socket outlet and input
cable.

Display Mode
code ”1” in LCD,
even though the
power supply is
available

Inverter

not

switched on

Press On-Switch “I”.

Display Mode
code ”3” in LCD, and
audible alarm
sounding every 1
beep in every 4
seconds

Mains power
supply has failed,
or Input power
and/or frequency
are out of tolerance

Switching to battery mode
automatically.
Check input power source
and inform dealer if
necessary.

Emergency supply
period shorter than
nominal value

Batteries not fully
charged / batteries
defect

Charge the batteries for at
least
5 - 8 hours and then check
capacity. If the problem still
persists, consult your
dealer.