7. Setting by LCD Module

The output voltage and frequency, and bypass state, and ECO mode, and

Converter mode could be set directly through LCD module. The output

voltage could be set to 208V, 220V, 230V and 240V. The output frequency

could be set to 50Hz and 60Hz. The operating mode of UPS could be set

between the Line mode, ECO mode and Converter mode. The bypass

state could be set to enable and disable. But all the settings could only be

done when the UPS is in bypass or no output mode.

In bypass or no output mode, pressing the “Select” button on the LCD

panel for more than one second, a flickering black dot would be shown

before “208V” on the screen. And if pressing the “Select” button

continuously again, the flickering black dot would move to “220V”, next to

“230V”, “240V”, “50Hz”, “60Hz”, “Bypass Disable”, “Bypass Enable”,

“UPS”, “ECO”, “CVF” in turn. (Here “UPS” means the normal inverter

mode, and “UPS”, “ECO”, and “CVF” would be presented circularly at the

position of output current) And if pressing the “Enter” button for more than

one second at this time, the flickering black dot would turn to flickerless

and the output voltage or frequency or bypass state or mode state setting

would be modified to the selected value. And if no any pressing on the

“Select” or “Enter” button lasting for more than 30 seconds, the flickering

black dot would disappear.

The only one voltage value could be selected in “208V”, “220V”, “230V”,

“240V” at any time. The only one frequency value could be selected in

“50Hz”, “60Hz” at any time. And the output voltage and frequency would

be changed to the corresponding value after the right values are selected

on the LCD panel and the UPS is turn on by pressing the “ON” Button.

The UPS would turn to bypass mode in several seconds after “Bypass

Enable” is selected, and turn to no output mode in several seconds after

“Bypass Disable” is selected. The mode change would be active only after

the UPS is turned on.