31

9. Maintenance

9.1 Operation

The UPS system contains no user-serviceable parts. If the battery

service life (3~5 years at 25°C ambient temperature) has been

exceeded, the batteries must be replaced. In this case please contact

your dealer.

9.2 Storage

If the batteries are stored in temperate climatic zones, they should be

charged every three months for 1~2 hours. You should shorten the

charging intervals to two months at locations subject to high

temperatures.

9.3 Battery Replace

If the battery service life has been exceeded, the batteries must be

replaced.

Battery replacement should be performed only by qualified

personnel.

It recommends to shut off the UPS completely before the replacement.

If there is a battery breaker then turn it off first. Disconnect the battery

cable carefully and make sure no any exposed wires can be touched.

Reconnect the new batteries to the UPS by following section 5.8.

Then turn on the battery breaker and press the ON switch to make the

UPS do the battery test, check whether the battery information is

normal.