En table 10 fault code/ audible alarm – PowerWalker Inverter 3000 PSW User Manual
Page 19
16
EN
Table 10 Fault code/ Audible alarm
Operate
Condition
--
Low DC
Voltage
Alarm
Inverter DC voltage 1beep/2s -- -- -- 0 Low DC Inverter DC Voltage -- Beep continuous Auto Mains is normal 1 Over Line DC Voltage>High DC input Beep continuous -- Manual -- 1 Over Standby DC Voltage>High DC input -- Beep continuous Auto DC Voltage DC input Shut-down Recovery Line/ Inverter 110%~150% load 1beep/0.5s,and continuous 10s Beep continuous Manual -- Line/ Inverter >150% load 1beep/0.5s,and continuous 5s Beep continuous Manual -- 3 Output Inverter 1)Output Voltage<20Vrms ℃ -- Beep continuous Manual -- 4 Fan Fault Line/ Inverter Fan Locked 2beep/2s, and continous 1min Beep continuous Manual -- 5 Over Line/ Inverter HEAT SINK Temp ≥ 100 ℃ -- Beep continuous Auto HEAT SINK Temp ≤ 55 ℃ 6 Output Inverter 1)Output Voltage<170Vrms ℃ -- Beep continuous Manual -- Fault (O/P=OFF) Restart 2 Over Load Active Mode Condition Warning (O/P=ON) Fault Code Protect Function
Voltage
Protection
Charge
Protection
Shut-down
Voltage
Protection
Shut-down
Short
Circuit
Protection
2)TX temperature>102
Protection
Fan Defected
Temp
Protection
Abnormal
or Output Voltage>250Vrms
2)TX temperature>102
Protection