AC Connections

Installation should be done by a qualified electrician. Consult local code for the proper wire sizes,

connectors and conduit requirements.

On the left of rear chassis is the AC hardwire cover. Two three-station terminal block is provided to make

the AC connections. The terminal block is used to hardwire the AC input, AC output, and ground. The

National Electrical Code requires that an external disconnect switch be used in the AC input wiring circuit.

The AC breakers in a sub panel will meet this requirement.

Step 1: Disconnect the unit from the battery by removing the battery cables from the battery. Turning off

the unit does not constitute disconnecting from the battery.

Figure 5 AC Cable Connect to unit

Step 2: Following the wiring guide located in the AC input wiring compartment as figure 5, connect the

GND (green/yellow), Line (brown), and neutral (blue) wires from the AC input (utility, generator,

etc) to the terminal block.

Caution!! Be sure that AC source is disconnected before attempting to hardwire it to the unit.

Step 3: Connect the AC Line output wiring to the terminal marked AC Line (output), following the wiring

guide inside the compartment. Torque the wires into the terminal block.