En table 6 invert mode specifications – PowerWalker Inverter 3000 PSW User Manual
Page 16
![background image](/manuals/284918/16/background.png)
13
EN
Table 6 Invert Mode Specifications
MODEL
PowerWalker Inverter 3000 PSW
Output Voltage Waveform
Pure Sine Wave
Rated Output Power
3000VA
Power Factor
0.8
Nominal Output voltage
230Vac
Minimum Peak Output Voltage at
Rated Power
>200V
Output Frequency(Hz)
50Hz / 60Hz ± 1Hz (follow first connect to grid)
Output Voltage Regulation
±10% Vrms
Nominal Efficiency
>90% (@Normal DC Input; >60% R load)
Over-Load Protection
fault after 5s@
≥
150% load,<=200% load
fault after 10s@110%~150% load,
Surge rating
6000VA
Capable of starting electric motor
1.5HP
Output Short Circuit Protection
Current limit (Fault after 4 cycles max)
Nominal DC Input Voltage
24V
Min DC start voltage
20V
Low DC Alarm
21.0 ± 0.6Vdc
Low DC Alarm Recovery
21.6 ± 0.6Vdc
Low DC Shut-down
20.0 ± 0.6Vdc
Low DC Shut-down Recovery
22.0 ± 0.6Vdc
High DC Shut-down
30.0 ± 0.6Vdc
High DC Shut-down Recovery
29.0 ± 0.6Vdc
DC component of output
<100mV
Power Limitation