B&B Electronics SDR-240 Series - Datasheet User Manual
Sdr-240, Series, Specification

SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
Note.6
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
Note.8
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
HARMONIC CURRENT
EMS IMMUNITY
WORKING TEMP.
Note.5
DC OK REALY CONTACT RATINGS (max.)
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSION
OTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1500ms, 60ms/230VAC
30
at full load
00ms, 60ms/115VAC
20ms/230VAC
20ms/115VAC at full load
88 ~ 264VAC
124 ~ 370VDC
47 ~ 63Hz
94%
0.93/230VAC
0.99/115VAC at full load
2.6A/115VAC
1.3A/230VAC
56 ~ 65V
33A/115VAC
65A/230VAC
<1mA / 240VAC
Normally w
more than 3
and then shut down o/p voltage with auto-recovery
orks within 110 ~ 150% rated output power for
seconds
29 ~ 33V
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
Protection type : Shut down o/p voltage with auto-recovery
95
5
(TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
UL508 TUV EN60950-1 approved
,
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level,
criteria A, SEMI F47, GL approved
-25 ~ +70
(Refer to output load derating curve)
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
20 ~ 95% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/
(0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
169.3Khrs min.
MIL-HDBK-217F (25
)
63*125.2*113.5mm (W*H*D)
1.03Kg; 12pcs/13.4Kg/1.06CUFT
POWER FACTOR (Typ.)
SDR-240-48
48V
5A
0 ~ 5A
240W
7.5A
120mVp-p
48 ~ 55V
1.0%
0.5%
1.0%
SDR-240-24
24V
10A
0 ~ 10A
240W
15A
360W (3sec.)
100mVp-p
24 ~ 28V
1.0%
0.5%
1.0%
Features :
SDR-240
series
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25
/ 70% RH
EMI CONDUCTION & RADIATION
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE
Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25
of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. After 30 minutes of burn-in.
240W Single Output Industrial DIN RAIL with PFC Function
Marine
GL
High efficiency 94% and low power dissipation
Built-in active PFC function, PF>0.93
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
150% peak load capability
Built-in DC OK relay contact
PQ
S
E
M
I F
4
7