485drci-ph – B&B Electronics 485DRCI-PH - Datasheet User Manual
Page 2

International Office: 707 Dayton Road PO Box 1040 Ottawa, IL 61350 USA 815-433-5100 Fax 433-5104
European Office: Westlink Commercial Park Oranmore Co. Galway Ireland +353 91 792444 Fax +353 91 792445
heavy industrial rS-232 to
rS-422/485 isolated Converter
485DRCI-PH
ieC 61850-3 eLeCtro magnetiC interFerenCe SpeCiFiCationS
test
desCriPtion
test level
level
61000-4-2
ESD
Enclosure Contact
8 kV
4
Enclosure Air
15 kV
4
61000-4-3
Radiated RFI
Enclosure Ports
10 V/m
3
61000-4-4
Burst (Fast Transient)
Signal Ports
4 kV @ 2.5 Khz
------
DC Power Ports
4 kV
4
61000-4-5
Surge
Signal Ports
2 kV line to earth, 1 kV line to line
4
DC Power Ports
2 kV line to earth, 1 kV line to line
3
61000-4-6
Induced (Conductive) RFI
Signal Ports
10 V RMS
3
DC Power Ports
10 V RMS
3
61000-4-12
Damped Oscillatory
Signal Ports
2.5 kV common, 1 kV diff mode @ 1MHz
3
DC Power Ports
2.5 kV common, 1 kV diff mode @ 1MHz
3
61000-4-16
Mains Frequency Voltage
Signal Ports
30 V Continuous, 300 V for 1 s
4
DC Power Ports
30 V Continuous, 300 V for 1 s
4
61000-4-17
Ripple on DC Power Supply
DC Power Ports
10%
3
ieee 1613 C37.90 eLeCtromagnetiC interFerenCe SpeCiFiCationS
test
desCriPtion
test level
level
C37.90.3
ESD
Enclosure Contact
8 kV
------
Enclosure Air
15 kV
------
C37.90.2
Radiated RFI
Enclosure Ports
10 v/m
------
C37.90.1
Fast Transient
Signal Ports
4 kV @ 2.5 kHz
------
DC Power Ports
4 kV
------
environmentaL SpeCiFiCationS
test
desCriPtion
test level
level
60068-2-1
Cold Temperature
Test Ad
(-)40 C, 16 Hours
------
60068-2-2
Dry Heat
Test Bd
(+)85 C, 16 Hours
------
60068-2-30
Humidity (damp heat cycle)
Test Dd
90% (non-condensing) (+)55C, 6 Cycles
------
IEC 60068-2-6
Vibration
Test Fc
4G
Class 2
IEC 60068-2-27
Shock
Test Ea
50G
Class 2
IEC 60068-2-32
Drop
------
6 faces, 3 edges, 1 corner total 10 drops at 1 m
------