D r - 6 0, 60w single output industrial din rail power supply, Specification

background image

SPECIFICATION

DR-60-5

DR-60-12

DR-60-15

DR-60-24

MODEL

DC VOLTAGE

RATED CURRENT

CURRENT RANGE

RATED POWER

OUTPUT

VOLTAGE ADJ. RANGE

LINE REGULATION

LOAD REGULATION

SETUP, RISE TIME

HOLD UP TIME (Typ.)

VOLTAGE RANGE

FREQUENCY RANGE

EFFICIENCY (Typ.)

AC CURRENT (Typ.)

INPUT

INRUSH CURRENT (Typ.)

SAFETY STANDARDS

HARMONIC CURRENT

EMS IMMUNITY

WORKING HUMIDITY

WORKING TEMP.

STORAGE TEMP., HUMIDITY

TEMP. COEFFICIENT

VIBRATION

MTBF

DIMENSION

OTHERS

NOTE

PACKING

OVERLOAD

OVER VOLTAGE

5V

12V

15V

24V

6.5A

4.5A

4A

2.5A

0 ~ 6.5A

0 ~ 4.5A

0 ~ 4A

0 ~ 2.5A

32.5W

54W

60W

60W

80mVp-p

120mVp-p

120mVp-p

13.5 ~ 16.5V

150mVp-p

21.6 ~ 26.4V

2.0%

1.0%

1.0%

1.0%

11.1 ~ 13.2V

4.75 ~ 5.5V

1.0%

1.0%

1.0%

1.0%

1.0%

1.0%

1.0%

1.0%

100ms, 30ms/230VAC

200ms, 30ms/115VAC at full load

100ms/230VAC

23ms/115VAC at full load

88 ~ 264VAC

124 ~ 370VDC

47 ~ 63Hz

76%

82%

83%

84%

1.2A/115VAC

0.8A/230VAC

COLD START 18A/115VAC

36A/230VAC

105 ~ 160% rated output power

Protection type : Constant current limiting, recovers automatically after fault condition is removed

5.75 ~ 6.75V

Protection type : Shut down o/p voltage, re-power on to recover

13.8 ~ 16.2V

17.25 ~ 20.25V

27.6 ~ 32.4V

-20 ~ +60

(Refer to output load derating curve)

20 ~ 90% RH non-condensing

-40 ~ +85

, 10 ~ 95% RH

0.03%/

(0 ~ 50

10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6

216.2K hrs min.

MIL-HDBK-217F (25

)

78*93*56mm (W*H*D)

0.3Kg; 48pcs/15.4Kg/1.02CUFT

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25

of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets

EMC directives.

File Name:DR-60-SPEC 2008-04-07

Compliance to EN55011,EN55022 (CISPR22) Class B

Compliance to EN61000-3-2,-3

Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A

60W Single Output Industrial DIN Rail Power Supply

D R - 6 0

s e r i e s

Universal AC input/Full range

Protections: Short circuit / Overload / Over voltage

Cooling by free air convection

Can be installed on DIN rail TS-35/7.5 or 15

UL 508(industrial control equipment)approved

Isolation class

LED indicator for power on

100% full load burn-in test

3 years warranty

Features :

RIPPLE & NOISE (max.)

Note.2

VOLTAGE TOLERANCE

Note.3

ENVIRONMENT

PROTECTION

SAFETY &

EMC

(Note 4)

WITHSTAND VOLTAGE

ISOLATION RESISTANCE

EMI CONDUCTION & RADIATION

I/P-O/P:3KVAC

I/P-O/P:100M Ohms/500VDC

UL60950-1, TUV EN60950-1 a

EN50178

pproved, Design refer to