Technical data kfd2-br-1.pa.93 – VEGA KFD2-BR-1.PA.93 Segment coupler for PROFIBUS PA User Manual
Page 2

2
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
Technical Data
KFD2-BR-1.PA.93
044
76
5_
EN
G.xm
l
2
003
-02-
2
7
Supply
Connection
Power Rail or terminals 47 (L+), 48 (L-)
Rated voltage
20 ... 35 V DC
Ripple
≤ 10 %
Rated current
790 mA ... 400 mA
Fieldbus connection
Profibus PA
Connection
terminals 3, 15+; 2, 14-
Rated voltage
24 ... 26 V
Rated current
≤ 400 mA
Terminating impedance
100
Ω , integrated
Profibus DP
PROFIBUS with RS 485 transmission technique
Connection
terminals 28 RxD/TxD-P, 29 RxD/TxD-N, 30 screen/FE, 40 DGND, 41 CNTR-P, 42 VP
Baudrate 93,75
kBit/s
Terminating impedance
with rotary switch (S1) switchable: 1 = on; 0 = off
Electrical isolation
Profibus PA/Profibus RS 485-Segment
safe electrical isolation acc. to EN 50020, voltage peak value 50 V
PROFIBUS DP/Supply
function insulation acc. to DIN EN 50178, rated insulation voltage 50 V
eff
PROFIBUS PA/Supply
safe electrical isolation acc. to EN 50020, voltage peak value 50 V
All circuits/FE
function insulation acc. to DIN EN 50178, rated insulation voltage 50 V
eff
Standard conformity
Electrical isolation
EN 50178
Electromagnetic compatibility
NAMUR NE 21
Protection degree
IEC/EN 60529
Fieldbus standard
EN 50170/2
Climatic conditions
DIN IEC 721
Directive conformity
Electromagnetic compatibility
Directive 89/336/EG
EN 61326, EN 50081-2
Ambient conditions
Classification
3K3
Ambient temperature
-20 ... 60 °C (253 ... 333 K)
Storage temperature
-40 ... 85 °C (233 ... 358 K)
Relative humidity
< 75 %
Degree of soiling
max. 2, according to IEC 664
Mechanical specifications
Connection type
terminals
Core cross-section
up to 2.5 mm
2
Housing
80 mm x 115 mm x 107 mm
Protection degree
IP20
Mass
600 g
Mounting
DIN rail mounting
Data for application in conjunction with
hazardous areas
Statement of conformity
pending
Accessories
Power Rail
UPR02
Power feed module
KFD2-EB2
Terminal resistor
KMD0-FT-Ex
Fx-FT-Ex1.I.IEC
Fx-FT-Ex1.D.IEC