VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Approval according to LPR radio standard User Manual
Page 57
Code
Text mes-
sage
Cause
Rectification
PA Dev-
Spec
Diagnosis
F
105
Determine
measured
value
l The instrument is still
in the start phase, the
measured value
could not yet be de-
termined
l Wait for the warm-up
phase
l Duration depending
on the version and
parameter adjust-
ment up to approxi-
mately 3 min.
Bit 6
F
113
Communi-
cation error
l Error in the internal
instrument communi-
cation
l Separate operating
voltage briefly
l Send instrument for
repair
Bit 7
F
125
Unpermis-
sible elect-
ronics tem-
perature
l Temperature of the
electronics in the
non-specified section
l Check ambient tem-
perature
l Isolate electronics
l Use instrument with
higher temperature
range
Bit 8
F
260
Error in the
calibration
l Error in the calibra-
tion carried out in the
factory
l Error in the EEPROM
l Exchange of the
electronics
l Send instrument for
repair
Bit 9
F
261
Error in the
configurati-
on
l Error during setup
l False signal sup-
pression faulty
l Error when carrying
out a reset
l Repeat setup
l Repeat reset
Bit 10
F
264
Installation/
Setup error
l Adjustment not within
the vessel height/
measuring range
l Max. measuring ran-
ge of the instrument
not sufficient
l Check or correct in-
stallation and/or pa-
rameter adjustment
l Use an instrument
with bigger measu-
ring range
Bit 11
F
265
Measure-
ment func-
tion distur-
bed
l Sensor does no lon-
ger carry out a mea-
surement
l Operating voltage too
low
l Check operating vol-
tage
l Carry out a reset
l Separate operating
voltage briefly
Bit 12
The following table shows the error codes and text messages in the
status message "Function check" and provides information on causes
as well as corrective measures.
Function check
VEGAPULS
61 • Approval according to LPR radio standard
57