beautypg.com

VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA Approval according to LPR radio standard User Manual

Page 21

background image

As an alternative, sensors with guided microwave can be used. These
are unaffected by foam generation and are best suited for such
applications.

When using a surge pipe in a vessel, influences from vessel
installations and turbulences can be excluded. Under these prereq-
uisites, the measurement of products with low dielectric values (ε

r

value ≥ 1.6) is possible. In very adhesive products, measurement in a
surge pipe is not recommended.

1

2

3

100%

4

5

8

6

7

0%

9

Fig. 16: Configuration surge pipe

1

Radar sensor

2

Marking of the polarisation direction

3

Thread or flange on the instrument

4

Vent hole

5

Holes

6

Weld joint

7

Welding neck flange

8

Ball valve with complete opening

9

Fastening of the surge pipe

Instructions for orientation:

l

Note marking of the polarisation plane on the sensor

Measurement in a surge
pipe

VEGAPULS

61 • Approval according to LPR radio standard

21

4 Mounting

41715

-

EN

-120301