6 Set up the sensor with the display and adjustment module

VEGAPULS SR 68 • Modbus and Levelmaster protocol

41371-EN-130624

Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].

Now select with [->] the menu item "Min. adjustment" and confirm

with [OK].

2. Edit the percentage value with [OK] and set the cursor to the

requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

4. Enter the suitable distance value in m for the empty vessel (e.g.

distance from the sensor to the vessel bottom) corresponding to

the percentage value.

5. Save settings with [OK] and move with [ESC] and [->] to the max.

adjustment.

Proceed as follows:
1. Select with [->] the menu item max. adjustment and confirm with

[OK].

2. Prepare the percentage value for editing with [OK] and set the

cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

Setup - Min. adjustment

Setup - Max. adjustment