beautypg.com

4 mounting instructions – VEGA VEGAPULS SR 68 Modbus and Levelmaster protocol User Manual

Page 16

background image

16

4 Mounting

VEGAPULS SR 68 • Modbus and Levelmaster protocol

41371-EN-130624

Note:

A damaged O-ring seal must be replaced: FKM (SHS FPM 70C3

GLT), FFKM (Kalrez 6375)
8. Remount the parabolic antenna (4)
9. Fasten compression nut (1) with a wrench (width across flats 41),

torque max. 50 Nm

10. Fasten counter nut (2) with a wrench (width across flats 36),

torque max. 40 Nm

Note:

On the version with rinsing air connection, make sure that the holes

in the antenna and in the process fitting coincide. This ensures a suf-

ficient air flow (the air is led through the holes to the feed system. A

rinsing of the whole parabolic antenna is not intended).

1

2
3

4

Fig. 7: Dismounting, parabolic antenna
1 Connection piece

2 Compression nut

3 Locknut

4 Parabolic antenna

4.4 Mounting instructions

The emitted radar impulses of the radar sensor are electromagnetic

waves. The polarisation is the direction of the electrical wave compo-

nent. By turning the instrument in the connection flange or mounting

boss, the polarisation can be used to reduce the effects of false

echoes.
The position of the polarisation is marked on the process fitting of the

instrument.

Polarisation