VEGA VEGAPULS SR 68 Modbus and Levelmaster protocol User Manual
Page 3
3
Quick start
VEGAPULS SR 68 • Modbus and Levelmaster protocol
41371-EN-130624
3. Select in the menu item "Application" the vessel, the application
and the vessel form, for example, silo.
4. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
The radar sensor as a distance measuring instrument measures the
distance from the sensor to the product surface. For indication of the
real level, an allocation of the measured distance to the percentage
height must be carried out.
2
1
100%
0%
1 m
(39.37
")
35 m (1378
")
Fig. 3: Parameterization example
1 Min. level ≙ max. meas. distance
2 Max. level ≙ min. meas. distance
For this adjustment, the distance is entered for min. and max. level.
If these values are not known, an adjustment with distances, for
example, of 10 % and 90 % is also possible. Starting point for these
distance specifications is always the seal surface of the thread or
flange.
1. In the menu "Additional settings", menu item "Damping" you can
adjust the requested damping of the output signal.
2. Select the output characteristics in the menu item "Current out-
put".
The quick start is then finished. For further information see chapter
"Parameter adjustment".
Parameterization example
Further steps