beautypg.com

4 proof test – VEGA VEGASWING 66 - two-wire With SIL qualification User Manual

Page 24

background image

24

6 Setup

VEGASWING 66 • - two-wire

44952-EN-130805

Sensor

Signal con-

ditioning

instrument

Mode on the

signal con-

ditioning

instrument

Level

Signal cur-

rent - Sensor

Signal lamp -

green
Voltage sup-

ply

Signal lamp -

yellow
Switching

status

Signal lamp

- red
Fault mes-

sage

Analogue

- input con-

trol

1)

Mode max.
Overflow pro-

tection

approx. 8 mA

> 3.8 mA
< 11.5 mA

Mode max.
Overflow pro-

tection

approx. 16 mA

> 12.5 mA
< 21.6 mA

Mode min.
Dry run pro-

tection

approx. 8 mA

> 3.8 mA
< 11.5 mA

Mode min.
Dry run pro-

tection

approx. 16 mA

> 12.5 mA
< 21.6 mA

Failure of the

supply volt-

age
Mode (max./

min.)

any

-

≤ 3.6 mA
≥ 21 mA

Fault message
Mode (max./

min.)

any

approx.

1.8 mA

≤ 3.6 mA
≥ 21 mA

6.4 Proof test

To find out possible undetected, dangerous failures, a proof test must

be carried out in adequate time intervals to check the safety function.

It is the user's responsibility to choose the type of testing.
You will find further instructions in the Safety Manual.
The following options are available for carrying out the proof test:
1. Short interruption of the supply line to the sensor or pushing the

test key (with function test).
Average coverage (detected errors)

2. Dismounting of the sensor and immersion in the original medium

High coverage (detected errors)

3. Filling of the vessel up to the switching point

1)

Electronics directly evaluated via the analogue input of a control system

(without signal conditioning instrument)