6 setup, 1 general information – VEGA VEGASWING 66 - two-wire With SIL qualification User Manual
Page 21
21
6 Setup
VEGASWING 66 • - two-wire
44952-EN-130805
6 Setup
6.1 General information
The figures in brackets refer to the following illustrations.
In the basic setting, products with a density ≥ 0.7 g/cm³ (0.025 lbs/in³)
can be detected. For products with lower density, you have to set the
switch to ≥ 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following display and
adjustment elements:
•
Signal lamps (1, 2, 3)
•
DIL switch for mode setting - min./max. (4)
•
DIL switch for sensitivity adjustment (5)
•
Test key (6)
Mode adjustment (min./max.)
On the signal conditioning instrument VEGATOR 536Ex, 537Ex,
636Ex, via the signal conditioning instrument.
The switching condition can be changed with the min./max. switch.
You can set the required mode according to the "Function chart"
(max. - max. detection or overfill protection, min. - min. detection or
dry run protection). The switching delay can also be modified on the
signal conditioning instrument (VEGATOR 536Ex, 537Ex and 636Ex
signal conditioning instruments).
If you want to carry out the mode adjustment via the signal condition-
ing instruments, you have to set the mode switch on the electronics
module of VEGASWING 66 to "max.".
Note:
For test purposes, immerse the tuning fork of VEGASWING 66 always
in liquids. Do not test the function of VEGASWING 66 with your hand.
This can damage the sensor.
Function/Configuration