11 Supplement

VEGAFLEX 83 • Modbus and Levelmaster protocol

41843-EN-130314

All commands start with "Uuu", whereby "uu" stands for the address (00-31)

"*" can be used as a joker for any position in the address. The sensor always converts this in

its address. In case of more than one sensor, the joker must not be used, because otherwise

several slaves will answer

Commands that modify the instrument return the command with "OK“. "EE-ERROR" replaces

"OK" if there was a problem changing the configuration

Report Level (and Temperature)

Request:

Parameter

Length

Code/Data

Report Level (and Temperature)

4 characters ASCII

Uuu?

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

24 characters ASCII

UuuDlll.llFtttEeeeeWwwww
uu = Address
lll.ll = PV in inches
ttt = Temperature in Fahrenheit
eeee = Error number (0 no error, 1

level data not readable)
wwww = Warning number (0 no

warning)

Level in inches is repeated for sensors with 2 levels. PV value is transmitted as first measured value,

SV as second measured value.
PV, SV, TV and QV can be adjusted via the sensor DTM.

Report Unit Number

Request:

Parameter

Length

Code/Data

Report Unit Number

5 characters ASCII

U**N?

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

6 characters ASCII

UuuNnn

Assign Unit Number

Request:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNnn

Response:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNOK
uu = new Address