VEGA VEGAFLEX 83 Modbus and Levelmaster protocol Polished version User Manual
Page 32
32
6 Set up with the display and adjustment module
VEGAFLEX 83 • Modbus and Levelmaster protocol
41843-EN-130314
In this menu item, you can select the application. You can choose
between level measurement and interface measurement. You can
also choose between measurement in a vessel or in a bypass or
standpipe.
Note:
The selection of the application has a considerable influence on all
other menu items. Keep in mind that as you continue with the param-
eter adjustment, individual menu items are only optionally available.
You have the possibility to choose the demonstration mode.This
mode is suitable for test and demonstration purposes. In this mode,
the sensor ignores the logic parameters of the application and reacts
immediately to each change.
In this menu item, you can define the medium type (product).
This menu item is only available if you have selected level measure-
ment under the menu item "Application".
You can choose between the following medium types:
Dielectric con-
stant
Medium type
Examples
> 10
Water-based liq-
uids
Acids, alcalis, water
3 … 10
Chemical mix-
tures
Chlorobenzene, nitro lacquer, aniline,
isocyanate, chloroform
< 3
Hydrocarbons
Solvents, oils, liquid gas
This menu item is only available, if you have chosen interface meas-
urement under the menu item "Application". In this menu item you can
enter if there is a superimposed gas phase in your application.
Only set the function to "Yes", if the gas phase is permanently pre-
sent.
Setup - Application - Ap-
plication
Setup - Application - Me-
dium, dielectric constant
Setup - Application - Gas
phase