3 modbus register, Holding register, Input register – VEGA VEGAFLEX 83 Modbus and Levelmaster protocol Polished version User Manual

Page 77

background image

77

11 Supplement

VEGAFLEX 83 • Modbus and Levelmaster protocol

41843-EN-130314

(4 bytes) according to IEEE 754 are transmitted with individually selectable order of the data bytes

(byte transmission order). This "Byte transmission order" is determined in the parameter "Format

Code". Hence the RTU knows the registers of the VEGAFLEX 83 which must be contacted for the

variables and status information.

Format Code

Byte transmission order

0

ABCD

1

CDAB

2

DCBA

3

BADC

11.3 Modbus register

Holding Register

The Holding registers consist of 16 bit. They can be read and written. Before each command, the

address (1 byte), after each command, a CRC (2 byte) is sent.

Register Name Register Num-

ber

Type

Configurable

Values

Default Value

Unit

Address

200

Word

1 … 255

246

-

Baud Rate

201

Word

1200, 2400,

4800, 9600,

19200

9600

-

Parity

202

Word

0 = None, 1 =

Odd, 2 = Even

0

-

Stopbits

203

Word

1 = None, 2 =

Two

1

-

Delay Time

206

Word

10 … 250

50

ms

Byte Oder (Float-

ing point format)

3000

Word

0, 1, 2, 3

0

-

Input register

The input registers consist of 16 bits. They can only be read out. Before each command, the ad-

dress (1 byte) is sent, after each command a CRC (2 bytes) is sent.
PV, SV, TV and QV can be adjusted via the sensor DTM.

Register Name

Register Number

Type

Note

Status

100

DWord

Bit 0: Invalid Measurement Value PV
Bit 1: Invalid Measurement Value SV
Bit 2: Invalid Measurement Value TV
Bit 3: Invalid Measurement Value QV

PV Unit

104

DWord

Unit Code

PV

106

Primary Variable in Byte Order CDAB

SV Unit

108

DWord

Unit Code

SV

110

Secondary Variable in Byte Order CDAB

TV Unit

112

DWord

Unit Code