beautypg.com

Level time 0 – VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire Rod probe - Polished version With SIL qualification User Manual

Page 69

background image

69

10 Diagnostics and service

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44225-EN-130823

Error

Cause

Rectification

4 … 20 mA signal

missing

– Electrical con-

nection faulty

– Check connection according to

chapter "Connection steps" and

if necessary, correct according to

chapter "Wiring plan"

– Voltage supply

missing

– Check cables for breaks; repair if

necessary

– Operating volt-

age too low or

load resistance

too high

– Check, adapt if necessary

Current sig-

nal greater than

22 mA or less

than 3.6 mA

– Electronics

module in the

sensor defec-

tive

– Exchange the instrument or send it

in for repair

The below tables show typical examples for application-relevant

measurement errors. There are two measurement errors:

Constant level

Filling

Emptying

The images in column "Error pattern" show the real level with a bro-

ken line and the level displayed by the sensor as a continuous line.

1
2

Level

time

0

Fig. 33: The broken line 1 shows the real level, the continuous line 2 shows the

level displayed by the sensor

Note:

Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"

In case of a too low level indication, the reason could be a line

resistance that is too high

Treatment of measure-

ment errors