beautypg.com

6 functional safety (sil), 1 objective, 2 sil qualification – VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire Rod probe - Polished version With SIL qualification User Manual

Page 29: 3 application area

background image

29

6 Functional safety (SIL)

VEGAFLEX 83 • 4 … 20 mA/HART two-wire

44225-EN-130823

6 Functional safety (SIL)

6.1 Objective

In case of dangerous outages, processing facilities and machines can

cause risks for persons, environment and property. The risk of such

outages must be judged by the plant operator. Dependent thereon are

measures for risk reduction through error prevention, error detection

and fault control.
The part of plant security depending on the correct functioning of

safety-related components for risk reduction is called functional

safety. Components used in such safety-instrumented systems (SIS)

must therefore execute their intended function (safety function) with a

defined high probability.
The safety requirements for such components are described in the

international standards IEC 61508 and 61511 (IEC 61062 - Ma-

chines), which set the standard for uniform and comparable judge-

ment of instrument and plant or machine safety and hence contribute

to worldwide legal certainty. Depending on the degree of required risk

reduction, we distinguish between four safety levels, from SIL1 for low

risk to SIL4 for very high risk (SIL = Safety Integrity Level).

6.2 SIL qualification

When developing instruments which can be used in safety-instru-

mented systems, the focus is on avoiding systematical as well as

determining and controlling random errors.
Here the most important characteristics and requirements from the

perspective of functional safety according to IEC 61508 (Edition 2):

Internal monitoring of safety-relevant circuit parts

Extended standardization of the software development

In case of failure, switching of the safety-relevant outputs to a

defined safe status

Determination of the failure probability of the defined safety func-

tion

Reliable parameterization with non-safe user environment

Proof test

The SIL qualification of components is specified in a manual for func-

tional safety (Safety Manual). Here, you can find all safety-relevant

characteristics and information required by the user and planner for

planning and operating the safety-relevant system. This document is

attached to each instrument with SIL rating and can be also retrieved

via the serial number search on our homepage.

6.3 Application area

The instrument can be used for point level detection or level measure-

ment of liquids and bulk solids in safety-instrumented systems (SIS)

according to IEC 61508, IEC 61511 and IEC 61062. Take note of the

specifications in the Safety Manual.
The following inputs/outputs are permitted:

Additional characteristics

and requirements