VEGA VEGAFLEX 83 4 … 20 mA_HART two-wire Rod probe - Polished version With SIL qualification User Manual
Page 3
3
Quick start
VEGAFLEX 83 • 4 … 20 mA/HART two-wire
44225-EN-130823
2. In the menu item "Medium - Dielectric constant" you can define
the medium type (medium).
3. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
4. A "Linearization" is recommended for all vessels in which the
vessel volume does not increase linearly with the level - e.g. in a
horizontal cylindrical or spherical tank. Activate the appropriate
curve.
5. A "False signal suppression" detects, marks and saves the false
signals so that they are no longer taken into account for level
measurement. We generally recommend a false signal suppres-
sion.
The sensor measures the distance from the sensor (reference plane)
to the product surface.
4
5
3
1
2
Fig. 3: Measuring ranges - VEGAFLEX 83
1 Reference plane
2 Probe length L
3 Measuring range (default setting refers to the measuring range in water)
4 Upper dead band (in this area no measurement is possible)
5 Lower dead band (in this area no measurement is possible)
For this adjustment, the distance is entered when the vessel is full
and nearly empty. If these values are not known, an adjustment with
other distances, for example, 10 % and 90 % is also possible. Starting
point for these distance specifications is always the seal surface of
the process fitting.
1. In the menu "Additional settings", menu item "Damping" you can
adjust the requested damping of the output signal.
Parameterization example
Further steps