10 Diagnostics and service
VEGAFLEX 83 • 4 … 20 mA/HART two-wire
44225-EN-130823
Code
Text mes-
sage
Cause
Rectification
C700
Simulation ac-
tive
– A simulation is active
– Finish simulation
– Wait for the automatic end
after 60 mins.
C701
Parameter
verification
– Parameter verification was
interrupted
– Finish parameter verifica-
tion
The following table shows the error codes and text messages in the
status message "Out of specification" and provides information on
causes as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
S600
Unpermissi-
ble electronics
temperature
– Temperature of the elec-
tronics in the non-specified
section
– Check ambient temperature
– Isolate electronics
– Use instrument with higher
temperature range
S601
Overfilling
– Danger of vessel overfilling
– Make sure that there is no
further filling
– Check level in the vessel
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
M500
Error with the
reset delivery
status
– With the reset to delivery
status, the data could not
be restored
– Repeat reset
– Load XML file with sensor
data into the sensor
M501
Error in the
non-active
linearization
table
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
M502
Error in the
diagnosis
memory
– Hardware error EEPROM
– Exchanging the electronics
– Send instrument for repair
Out of specification
Maintenance