beautypg.com

VEGA VEGAFLEX 81 Profibus PA User Manual

Page 51

background image

51

6 Set up with the display and adjustment module

VEGAFLEX 81 • Profibus PA

44217-EN-130910

Menu item

Default value

Modified value

Medium, dielectric constant

Water-based, > 10

Superimposed gas phase

Yes

Dielectric constant, upper medium (TS)

1.5

Tube inner diameter

200 mm

Max. adjustment - Level

100 %

Max. adjustment - Level

Distance: 0.000 m(d) - note block-

ing distances

Min. adjustment - Level

0 %

Min. adjustment - Level

Distance: Probe length - take dead

band into account

Accept adjustment of the level measurement?

Yes

Max. adjustment - Interface

100 %

Max. adjustment - Interface

Distance: 0.000 m(d) - note block-

ing distances

Min. adjustment - Interface

0 %

Min. adjustment - Interface

Distance: Probe length - take dead

band into account

Integration time - Level

0.0 s

Integration time - Interface

0.0 s

Linearization type

Linear

Linearization - Socket correction

0 mm

Linearization - Vessel height

Probe length

AI FB1 Tag Descriptor
AI FB1 Channel

Primary Value (lin. percent level)

AI FB1 scaling PV Scale (min.)

0 %

AI FB1 scaling PV Scale (max.)

100 %

AI FB1 Lin. Type

Linear

AI FB1 Out Scale Unit

%

AI FB1 Out Scale Decimal Point

#.##

AI FB1 Out Scale (min.)

0 %

AI FB1 Out Scale (max.)

100 %

AI FB1 PV FTime

0 s

AI FB1 Hi Hi Limit

3.402823E+38 %

AI FB1 Hi Limit

3.402823E+38 %

AI FB1 Lo Lo Limit

-3.402823E+38 %

AI FB1 Lo Limit

-3.402823E+38 %

AI FB1 Hysteresis

0.50 %