Quick start – VEGA VEGAFLEX 81 Profibus PA User Manual
Page 2
2
Quick start
VEGAFLEX 81 • Profibus PA
44217-EN-130910
Quick start
The quick start procedure enables a quick setup of the instrument
with many applications. You can find further information in the respec-
tive chapters of the operating instructions manual.
1. Distance from the metallic vessel wall > 300 mm. Distance from
non-metallic vessel wall > 500 mm. The probe must not touch any
installations or the vessel wall.
2. In non-metallic vessels, place a metal sheet beneath the process
fitting.
1
2
Fig. 1: Installation in non-metallic vessel
1 Flange
2 Metal sheet
3. If necessary, fasten probe end.
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-
tions on the type label.
2. Connect the instrument according to the following illustration
5
0
0
5
1
6
2
7
3
8
4
9
0
5
1
6
2
7
3
8
4
9
1
0
1
6 7 8
Bus
2
3
4
5
1
2
+
( )
(-)
1
Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output
2 For display and adjustment module or interface adapter
3 Selection switch for bus address
4 For external display and adjustment unit
5 Ground terminal for connection of the cable screen
For further information see chapter "Connecting to power supply".
For standard applications we recommend selecting the "Quick setup"
in the display and adjustment module.
Mounting
Electrical connection
Set parameters