beautypg.com

VEGA VEGAFLEX 81 Profibus PA User Manual

Page 3

background image

3

Quick start

VEGAFLEX 81 • Profibus PA

44217-EN-130910

1. In this menu item you can select the application. You can choose

between level and interface measurement.

2. In the menu item "Medium - Dielectric constant" you can define

the type of medium (medium).

3. Carry out the adjustment in the menu items "Min. adjustment" and

"Max. adjustment".

4. A "Linearization" is recommended for all vessels in which the

vessel volume does not increase linearly with the level - e.g. in a

horizontal cylindrical or spherical tank. Activate the appropriate

curve.

5. A "False signal suppression" detects, marks and saves the false

signals so that they are no longer taken into account for level

measurement. We generally recommend a false signal suppres-

sion.

The sensor measures the distance from the sensor (reference plane)

to the product surface. See also chapter "Parameter adjustment".

2

4

5

3

2

4

5

3

1

1

Fig. 3: Measuring ranges - VEGAFLEX 81
1 Reference plane

2 Probe length L

3 Measuring range (default setting refers to the measuring range in water)

4 Upper dead band (in this area no measurement is possible)

5 Lower dead band (in this area no measurement is possible)

For this adjustment, the distance is entered when the vessel is full

and nearly empty. If these values are not known, an adjustment with

other distances, for example, 10 % and 90 % is also possible. Starting

Parameterization example