VEGA VEGAFLEX 81 Profibus PA User Manual
Page 43
43
6 Set up with the display and adjustment module
VEGAFLEX 81 • Profibus PA
44217-EN-130910
be done with the lowest possible level so that all potential interfering
reflections can be detected.
Proceed as follows:
Enter the actual distance from the sensor to the product surface.
All interfering signals in this section are detected by the sensor and
stored.
Note:
Check the distance to the product surface, because if an incorrect
(too large) value is entered, the existing level will be saved as a false
echo. The filling level would then no longer be detectable in this area.
If a false signal suppression has already been created in the sensor,
the following menu window appears when selecting "False signal
suppression":
The instrument carries out an automatic false signal suppression
as soon as the probe is uncovered. The false signal suppression is
always updated.
The menu item "Delete" is used to completely delete an already cre-
ated false signal suppression. This is useful if the saved false signal
suppression no longer matches the metrological conditions in the
vessel.
A linearization is necessary for all vessels in which the vessel volume
does not increase linearly with the level - e.g. a horizontal cylindri-
cal or spherical tank, when the indication or output of the volume is
required. Corresponding linearization curves are preprogrammed
for these vessels. They represent the correlation between the level
percentage and vessel volume.
The linearization applies to the measured value indication and the
current output. By activating the appropriate curve, the volume per-
centage of the vessel is displayed correctly. If the volume should not
be displayed in percent but e.g. in l or kg, a scaling can be also set in
the menu item "Display".
Setup - Linearization