VEGA SOLITRAC 31 Profibus PA User Manual
Page 55
55
6 Set up with the display and adjustment module
SOLITRAC 31 • Profibus PA
43834-EN-131119
Menu
Menu item
Default value
Setup
Sensor address
126
Measurement loop name
Sensor
Isotope
Cs-137
Application
Limit level
Background radiation
0 ct/s
Temperature unit
° C
Adjustment mode
1-point
Adjustment (uncovered)
90000 ct/s
Delta I
90 %
AI FB1 Channel
Process value
AI FB1 scaling unit
%
AI FB1 scaling
0 % = 0 %
100 % = 100 %
AI FB1 damping
0 s
Mode relay
Dry run protection
Block adjustment
Released
Display
Language
Selected language
Displayed value
Pulse rate (ct/s)
With this function you can select the mode.
The sensor offers the HART modes standard and multidrop.
If the measured value is outputted via the 4 … 20 mA output, you
must not switch over to HART Multidrop.
The mode 'Standard', with fixed address 0 (factory setting), means
output of the measured value as 8/16 mA signal.
This parameter is described in the operating instructions manual
"Display and adjustment module".
With this function
•
Load parameter adjustment data from the sensor into the display
and adjustment module
•
Write parameter adjustment data from the display and adjustment
module into the sensor
This parameter is described in the operating instructions manual
"Display and adjustment module".
Info
In this menu you will find the following menu items:
•
Instrument name - shows instrument name and serial number
•
Instrument version - shows hardware and software version of the
instrument
Additional adjustments -
HART mode
Additional adjustments -
Copy instrument settings
Info