5 parameter adjustment - point level detection – VEGA SOLITRAC 31 Profibus PA User Manual
Page 45
45
6 Set up with the display and adjustment module
SOLITRAC 31 • Profibus PA
43834-EN-131119
Peak values of temperature: Resetting of the measured min. and
max. temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "Level". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Setup
Sensor address
126
Measurement loop name
Sensor
Isotope
Cs-137
Application
Summation Slave
Outputs
Deactivated
AI FB1 Channel
Process value
AI FB1 scaling unit
%
AI FB1 scaling
0 % = 0 %
100 % = 100 %
AI FB1 damping
0 s
Block adjustment
Released
Display
Language
Selected language
Displayed value
Pulse rate (ct/s)
6.5 Parameter adjustment - Point level detection
The instrument is adapted to the application conditions via the pa-
rameter adjustment. The parameter adjustment is carried out with an
adjustment menu.
Information:
In this operating instructions manual, the instrument-specific param-
eters are described. Further general parameters are described in the
operating instructions manual "Display and adjustment module".
Caution:
During the first setup or after an instrument reset the instrument starts
with preset standard values. These value are not suitable for your ap-
plication and must be replaced by real values.
Carry out a setup in the sequence described in the following.
The main menu is divided into five sections with the following func-
tions:
Setup: Settings, e.g. for measurement loop name, isotope, applica-
tion, background radiation, adjustment, signal output
Instrument start
Main menu