beautypg.com

5 set instrument address – VEGA SOLITRAC 31 Profibus PA User Manual

Page 26

background image

26

5 Connecting to power supply

SOLITRAC 31 • Profibus PA

43834-EN-131119

Information:

For example, a radial connection would be also possible as an alter-

native. Take note of the polarity.
The selection of the two terminal pairs is individual.

5.5 Set instrument address

An address must be assigned to each Profibus PA instrument. The

approved addresses are between 0 and 126. Each address must

only be assigned once in the Profibus PA network. The sensor is only

recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-

dress can be used for function test of the instrument and for con-

nection to a Profibus PA network. Then address must be changed to

integrate additional instruments.
The address setting is carried out either via:

The address selection switch in the electronics compartment of

the instrument (address setting via hardware)

The display and adjustment module (address setting via software)

PACTware/DTM (address setting via software)

The hardware addressing is effective if an address <126 is adjusted

with the address selection switches on the instrument. Hence the

software addressing is no longer effective, the adjusted hardware

address is valid.

2

1

3

1

1

2

4

5

6

22

11

12

21

22

19

20

18 17

14 13

16 15

12

9 10 11

Fig. 16: Address selection switch
1 Addresses <100 (selection 0), addresses >100 (selection 1)

2 Decade of the address (selection 0 to 9)

3 Unit position of the address (selection 0 to 9)

The software addressing is only effective if address 126 or higher is

adjusted on the instrument with the address selection switches.
The addressing procedure is described in the operating instructions

manual "Display and adjustment module.

Instrument address

Hardware addressing

Software addressing