6 Set up with the display and adjustment module

SOLITRAC 31 • Profibus PA

43834-EN-131119

In menu item"Channel" you determine which measured value the

output refers to.

In menu item "Scaling unit" you define the scaling variable and the

scaling unit for the pulse rate on the display, e.g. volume in percent.

In menu item "Scaling" you define the scaling format on the display

and the scaling of the measured values for 0 % and 100 %.

Measured value min.

Measured value max.

To damp process-dependent measured value fluctuations, you can

set a time of 0 … 999 s in this menu item.

The default setting is a damping of 0 s.

In this menu item you can select which mode the sensor should oper-

ate in.
You can choose between overfill and dry run protection.
The relay outputs of the sensor react accordingly.
Overfill protection = the relay will deenergise (safe condition) when

the max. level is reached.
Dry run protection = the relay will deenergise (safe condition) when

the min. level is reached.

Setup - AI FB1 - Channel

Setup - AI FB1 - Scaling

unit

Setup - AI FB1 - Scaling

Setup - AI FB1 - Damping

Setup - Relay