beautypg.com

VEGA VEGAFLEX 81 4 … 20 mA_HART two-wire Coax probe With SIL qualification User Manual

Page 76

background image

76

12 Supplement

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

44216-EN-130823

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

5)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

No gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

± 5 mm (0.197 in)

Typical deviation - Level measurement

6)7)

See following diagrams

Max. deviation - Version with reference

distance

± 10 mm (0.39 in)

Deviating upper dead band - Version with

reference distance

450 mm (17.7 in)

L

0

-2 mm (-0.079

")

2 mm (0.079

")

-10 mm (0.394

")

5 mm (0.197

")

0,15 m (5.906

"

)

0,03 m (1.181

"

)

0,05 m

(1.969

")

1

Fig. 39: Deviation VEGAFLEX 81 in coax version in water
1 Dead band - no measurement possible in this area

L Probe length

5)

With interface measurement = 2.0

6)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

7)

The dead bands can be optimizes by a false signal suppression.