beautypg.com

3 status messages – VEGA VEGAFLEX 81 4 … 20 mA_HART two-wire Coax probe With SIL qualification User Manual

Page 62

background image

62

10 Diagnostics and service

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

44216-EN-130823

Switch-on and switch-off times

Status messages (according to NE 107)

Error messages (according to NE 107)

The data are read out via a PC with PACTware/DTM or the control

system with EDD.

The echo curves are stored with date and time and the corresponding

echo data. The memory is divided into two sections:
Echo curve of the setup: This is used as reference echo curve for

the measurement conditions during setup. Changes in the measure-

ment conditions during operation or buildup on the sensor can thus

be recognized. The echo curve of the setup is stored via:

PC with PACTware/DTM

Control system with EDD

Display and adjustment module

Further echo curves: Up to 10 echo curves can be stored in a ring

buffer in this memory section. Further echo curves are stored via:

PC with PACTware/DTM

Control system with EDD

Display and adjustment module

10.3 Status messages

The instrument features self-monitoring and diagnostics according

to NE 107 and VDI/VDE 2650. In addition to the status messages in

the following tables there are more detailed error messages available

under the menu item "Diagnostics" via the display and adjustment

module, PACTware/DTM and EDD.

The status messages are divided into the following categories:

Failure

Function check

Out of specification

Maintenance requirement

and explained by pictographs:

4

1

2

3

Fig. 28: Pictographs of the status messages
1 Failure - red

2 Out of specification - yellow

3 Function check - orange

4 Maintenance - blue

Echo curve memory

Status messages