VEGA VEGAFLEX 81 4 … 20 mA_HART two-wire Coax probe With SIL qualification User Manual
Page 43
43
7 Set up with the display and adjustment module
VEGAFLEX 81 • 4 … 20 mA/HART two-wire
44216-EN-130823
In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 … 20 mA, failure mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
If a supplementary electronics with a second current output is im-
plemented in the instrument, then you can adjust the second current
output separately.
In menu item"Current output 2" you specify which measured value
the second current output refers to.
The second current output cannot be used as an output in the sense
of a safety-instrumented application (SIL).
The procedure corresponds to the previous settings of the standard
current output. See "Setup - Current output".
Since the HART variables are very extensive, the indication was
divided into two menu items.
Setup - Current output
mode
Setup - Current output
Min./Max.
Setup - Current output 2
Setup - HART variables
(1)