VEGA VEGAFLEX 81 4 … 20 mA_HART two-wire Coax probe With SIL qualification User Manual
Page 44
44
7 Set up with the display and adjustment module
VEGAFLEX 81 • 4 … 20 mA/HART two-wire
44216-EN-130823
In the menu "HART variables 1" you can have the first HART value PV
(primary value) and the second HART value SV (secondary value) of
the sensor displayed.
The values cannot be changed in the display and adjustment module.
To change these values, you have to use the adjustment software
PACTware.
HART functions are not relevant for SIL applications.
In the menu "HART variables 2" you can have the third HART value
TV (third value) and the fourth HART value QV (quarter value) of the
sensor displayed.
The values cannot be changed in the display and adjustment module.
To change these values, you have to use the adjustment software
PACTware.
HART functions are not relevant for SIL applications.
The following circumstances cause interfering reflections and can
influence the measurement:
•
High sockets
•
Vessel installations such as struts
Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account for the level and
interface measurement. We generally recommend carrying out a false
signal suppression to achieve the best possible accuracy. This should
be done with the lowest possible level so that all potential interfering
reflections can be detected.
Proceed as follows:
Enter the actual distance from the sensor to the product surface.
All interfering signals in this section are detected by the sensor and
stored.
Setup - HART variables
(2)
Setup - False signal sup-
pression