VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44234-EN-130823

Ʋ Displayed value 2

Electronics temperature

Resolution, digital

< 1 mm (0.039 in)

Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1

Ʋ Temperature

+18 … +30 °C (+64 … +86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

+860 … +1060 mbar/+86 … +106 kPa

(+12.5 … +15.4 psig)

Installation reference conditions

Ʋ Min. distance to installations

> 500 mm (19.69 in)

Ʋ Vessel

metallic, ø 1 m (3.281 ft), centric installation, process

fitting flush with the vessel ceiling

Ʋ Medium

Water/Oil (dielectric constant ~2.0)

4)

Ʋ Installation

Probe end does not touch the vessel bottom

Sensor parameter adjustment

No gating out of false signals carried out

Typical deviation - Interface measure-

ment

± 5 mm (0.197 in)

Typical deviation - Total level interface

measurement

See following diagrams

Typical deviation - Level measurement

5)6)

See following diagrams

L

0

-2 mm (-0.079")

2 mm (0.079")

15 mm (0.591")

-5 mm (-0.197")

0,3 m

(11.811")

0,08 m

(3.15")

1

0,015 m

(0.591")

Fig. 48: Deviation VEGAFLEX 86 in rod version in water
1 Dead band - no measurement possible in this area

L Probe length

4)

With interface measurement = 2.0

5)

Depending on the installation conditions, there can be deviations which can be rectified with an adaptation of

the adjustment or a change of the measured value offset in the DTM service mode

6)

The dead bands can be optimizes by a false signal suppression.