7 Set up with the display and adjustment module
VEGAFLEX 86 • 4 … 20 mA/HART two-wire
44234-EN-130823
Menu item
Default value
Modified value
Device memory - Measured value memory - Start
with measured value
Not active
Device memory - Measured value memory - Stop
with measured value
Not active
Device memory - Measured value memory - Stop
recording when memory is full
Not active
Additional adjustments
Menu item
Default value
Modified value
PIN
0000
Date
Actual date
Time
Actual time
Time - Format
24 hours
Probe type
Device-specific
HART mode
Analogue current output
The instrument settings are copied with this function. The following
functions are available:
•
Read from sensor: Read data from sensor and store into the
display and adjustment module
•
Write into sensor: Store data from the display and adjustment
module back to the sensor
The following data or settings for adjustment of the display and ad-
justment module are saved:
•
All data of the menu "Setup" and "Display"
•
In the menu "Additional adjustments" the items "Reset, Date/Time"
•
Special parameters
The copied data are permanently saved in an EEPROM memory in
the display and adjustment module and remain there even in case of
power failure. From there, they can be written into one or more sen-
sors or kept as backup for a possible electronics exchange.
Note:
Before the data are stored in the sensor, a check is carried out to
determine if the data fit the sensor. If the data do not fit, a fault signal
is triggered or the function is blocked. When data are being written
into the sensor, the display shows which instrument type the data
originate from and which TAG-no. this sensor had.
In this menu item you can select the type and size of your probe from
a list of all possible probes. This is necessary to adapt the electronics
optimally to the probe.
Additional adjustments -
Copy instrument settings
Additional adjustments -
Probe type