4 Mounting

VEGAFLEX 86 • 4 … 20 mA/HART two-wire

44234-EN-130823

1

2

1

2

Fig. 14: Fasten the probe
1 Probe

2 Retaining sleeve

In case of difficult installation conditions, the probe can be also

mounted laterally. For this purpose, adapt the rod with rod extensions

or bow-shaped segments.
Let the probe length determine automatically by the instrument to

compensate the resulting running time changes.
The determine probe length can deviate from the actual probe length

when using bow-shaped segments.
If installations such as struts, ladders, etc. exist on the vessel wall,

then the probe should have a distance to the vessel wall of at least

300 mm (11.81 in).
You can find further information in the supplementary instructions of

the rod extension.

In case of difficult installation conditions, for example in a socket, the

probe can be adapted respectively with a rod extension.
Let the probe length determine automatically by the instrument to

compensate the resulting running time changes.
You can find further information in the supplementary instructions of

the rod extension.

Vapours, superimposed gases, high pressures and temperature dif-

ferences can change the spreading speed of radar impulses.
There are two possibilities to correct these deviations.
Corrective value in the process control system

In the technical data under "Influence of superimposed gas and pres-

sure on accuracy" you can find a table with deviation values in some

typical gases or in steam.

Lateral installation

Rod extension

Steam boiler applications