The quick start procedure enables a quick setup with many applica-

tions. You can find further information in the respective chapters of the

operating instructions manual.
1. Distance from the metallic vessel wall > 300 mm. Distance from

non-metallic vessel wall > 500 mm. The probe must not touch any

installations or the vessel wall.

2. In non-metallic vessels, place a metal sheet beneath the process

fitting.

1

2

Fig. 1: Installation in plastic silo
1 Flange

2 Metal sheet

3. If necessary, fasten probe end.
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

5

1

2

+

( )

(-)

6 7 8

4...20mA

2

3

4

1

Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output

2 For display and adjustment module or interface adapter

3 For external display and adjustment unit

4 Ground terminal for connection of the cable screen

See also chapter "Connecting to power supply"
1. In this menu item you can select the application. You can choose

between level and interface measurement.

Mounting

Electrical connection

Set parameters