7 Setup with PACTware

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

42279-EN-130612

(Device Type Manager). This enables additional and special settings

over and above those offered by quick setup.
Maintenance

Under the menu item "Maintenance" you get comprehensive and

important support for servicing and maintenance. You can call up

diagnostic functions and carry out an electronics exchange or a

software update.

Click to the button "Quick setup", to start the assistant-driven adjust-

ment for a simplified and reliable setup.
Device name

Here, you can find the instrument name. You cannot change this line

because the instrument name is unmodifiably saved in the instrument.
Serial number

Here, you can find the serial number of your instrument. You cannot

change this line because the serial number is unmodifiably saved in

the instrument.
Measurement loop name

Here you can enter a suitable measurement loop name for your VE-

GAFLEX 81. You can enter a name with max. 19 characters. You can

use capital and small letters as well as numbers. The following special

characters are also possible: + - . : , ( ) / < >
Probe length modified?

If you have modified the probe length, this must be entered in the

selection field.

If you select "No", then the instrument uses automatically the

preset length of the default setting.

If you select "Yes", then you can enter in another field the modified

length of the instrument.

Probe length L from seal surface

If you have modified the length of the probe, you can enter in this field

the modified probe length. Keep the selected unit in mind.
Determine probe length automatically

If you do not know the probe length, you can have the length of the

probe determined automatically. The requirement for this is a probe

unrestricted and not covered by the medium.
Click to "Carry out now", to start the automatic length determination.
Medium type

Here you can see which medium type your instrument is suitable for.

If this function is inactive, the medium type your instrument is suitable

for was already preset.
Information:

In special cases you can change the medium type. This setting can be

changed under "Extended adjustment".

Start quick setup

Step 1

Instrument configuration

Step 2

Application