6 Set up with the display and adjustment module

VEGAFLEX 81 • 4 … 20 mA/HART two-wire

42279-EN-130612

Select the requested simulation size and adjust the requested value.

Caution:

During simulation, the simulated value is outputted as 4 … 20 mA cur-

rent value and digital HART signal.
Push the [ESC] key to deactivate the simulation.
Information:

The simulation is terminated automatically 60 minutes after the last

key has been pushed.

With the menu item "Setup" the echo curve it is possible to save at

the time of setup. This is generally recommended; for using the Asset

Management functions it is necessary. If possible, the curve should

be saved with a low level in the vessel.
With this, you can detect signal changes over the operating time. With

the adjustment software PACTware and the PC, the high-resolution

echo curve can be displayed and used to compare the echo curve of

the setup with the actual echo curve.

The function "Echo curve memory" enables storing echo curves of

the measurement.
Under the sub-menu item "Echo curve memory" you can store the

current echo curve.
Parameter settings for recording the echo curve and the settings of

the echo curve itself can be carried out in the adjustment software

PACTware.
With the adjustment software PACTware and the PC the high-reso-

lution echo curve can be displayed and used later on to assess the

quality of the measurement.

Entering a 4-digit PIN protects the sensor data against unauthorized

access and unintentional modification. In this menu item, the PIN is

displayed or edited and changed. However, this menu item is only

Diagnostics - Echo curve

memory

Additional settings - PIN