6 Set up with the display and adjustment module
VEGAFLEX 81 • 4 … 20 mA/HART two-wire
42279-EN-130612
available if adjustment is enabled in the menu "Lock/Release setup/
adjustment".
In delivery status, the PIN is "0000".
In this menu item, the internal clock of the sensor is adjusted.
With a reset, certain parameter adjustments carried out by the user
are reset.
The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of ship-
ment from the factory incl. the order-specific settings. A created false
signal suppression, user-programmable linearization curve as well as
the measured value memory will be deleted.
Basic settings: Resetting the parameter settings incl. special pa-
rameters to the default values of the respective instrument. A created
false signal suppression, user programmable linearization curve as
well as the measured value memory will be deleted.
The following table shows the default values of the instrument. De-
pending on the instrument version or application, all menu items may
not be available or some may be differently assigned:
Setup
Menu item
Default value
Modified value
Block adjustment
Released
Measurement loop name
Sensor
Units
Distance unit: mm
Temperature unit: °C
Probe length
Length of the probe Ex factory
Medium type
Liquid
Application
Level, vessel
Additional adjustments -
Date Time
Additional adjustments
- Reset