6 Set up the sensor with the indicating and adjustment module

VEGAPULS 65 • Modbus and Levelmaster protocol

41365-EN-121011

The menu item "Delete" is used to completely delete an already cre-

ated false signal suppression. This is useful if the saved false signal

suppression no longer matches the metrological conditions in the

vessel.
The menu item "Extend" is used to extend an already created false

signal suppression. This is useful if a false signal suppression was

carried out with a too high level and not all false signals could be de-

tected. When selecting "Extend", the distance to the product surface

of the created false signal suppression is displayed. This value can

now be changed and the false signal suppression can be extended to

this range.

A linearisation is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. in a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearisation curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. By activating the appropriate curve, the

volume percentage of the vessel is displayed correctly. If the volume

should not be displayed in percent but e.g. in l or kg, a scaling can be

also set in the menu item "Display".

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [ESC] and [->] key.

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language, lighting, SIL and HART

mode.

The following reset functions are available:

Delivery status: Restoring the parameter settings at the time

of shipment from the factory. A created false signal suppression,

user-programmable linearization curve, measured value memory

as well as event memory will be deleted.

Basic settings: Resetting of the parameter settings incl. special

and laboratory parameters to the default values of the respective

instrument. Any created false signal suppression, user program-

mable linearization curve, measured value memory as well as

event memory will be deleted.

Additional adjustments/

Linearization curve

Additional adjustments/

Reset