2 protocol description, 2 parameters for the bus communication, 2 general configuration of the host – VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual

Page 66: The vegapuls 61 is preset with the default values, Start bits and data bits cannot be modified

background image

66

11 Supplement

VEGAPULS 61 • Modbus and Levelmaster protocol

41361-EN-121011

4

1

3

3

3

2

+

+

power supply

MODBUS

D0

D1

IS GND

USB

+

+

power supply

MODBUS

D0

D1

IS GND

USB

+

+

power supply

MODBUS

D0

D1

IS GND

USB

1

3 4 5

2

off on

( )

(

)

(-)

(-)

1

3 4 5

2

off on

( )

(

)

(-)

(-)

1

3 4 5

2

off on

( )

(

)

(-)

(-)

Fig. 54: Bus architecture Modbus
1 RTU

2 Connection resistor

3 Bus participant

4 Voltage supply

11.2 Protocol description

The VEGAPULS 61 is suitable for connection to the following RTUs with Modbus RTU or ASCII

protocol.

RTU

Protocol

ABB Totalflow

Modbus RTU, ASCII

Bristol ControlWaveMicro

Modbus RTU, ASCII

Fisher ROC

Modbus RTU, ASCII

ScadaPack

Modbus RTU, ASCII

Thermo Electron Autopilot

Modbus RTU, ASCII

11.2 Parameters for the bus communication

The VEGAPULS 61 is preset with the default values:

Parameter

Configurable Values

Default Value

Baud Rate

1200, 2400, 4800, 9600, 19200

9600

Start Bits

1

1

Data Bits

7, 8

8

Parity

None, Odd, Even

None

Stop Bits

1, 2

1

Address range Modbus

1 … 255

246

Start bits and data bits cannot be modified.

11.2 General configuration of the host

The data exchange with status and variables between field device and host is carried out via