VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol User Manual
Page 62
62
11 Supplement
VEGAPULS 61 • Modbus and Levelmaster protocol
41361-EN-121011
Ʋ Protocols
Modbus RTU, Modbus ASCII, Levelmaster
Max. transmission rate
9.6 Kbit/s
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Installation reference conditions
Ʋ Min. distance to installations
> 200 mm (7.874 in)
Ʋ Reflector
Plane plate reflector
Ʋ False reflections
Largest false echo 20 dB smaller than the useful echo
Deviation with liquids
See following diagrams
0,5 m (1.6 ft)
10 mm (0.394 in)
- 10 mm (- 0.394 in)
2 mm (0.079 in)
- 2 mm (- 0.079 in)
0
1 2
3
Fig. 52: Deviation under reference conditions - encapsulated antenna system
1 Reference plane
2 Antenna edge
3 Recommended measuring range
0,5 m (1.6 ft)
10 mm (0.394 in)
- 10 mm (- 0.394 in)
2 mm (0.079 in)
- 2 mm (- 0.079 in)
0
1 2
3
Fig. 53: Deviation under reference conditions - plastic horn antenna
1 Reference plane
2 Antenna edge
3 Recommended measuring range
Reproducibility
≤ ±1 mm