beautypg.com

8 maintenance and fault rectification, 1 maintenance, 2 remove interferences – VEGA VEGAWELL 52 4 … 20 mA_HART Pt 100 User Manual

Page 26: 8maintenance and fault rectification

background image

8

Maintenance and fault rectification

8

.1 Maintenance

I

f the instrument is used properly, no special maintenance is required

in normal operation.

I

n some applications, product buildup on the diaphragm can influence

the measuring result. Depending on the sensor and application, take
precautions to ensure that heavy buildup, and especially a hardening
thereof, is avoided.

I

f necessary, clean the diaphragm. Make sure that the materials are

resistant to the cleaning process, see resistance list under "Services"
on "www.vega.com". The wide variety of applications of isolating
diaphragms makes special cleaning instructions necessary for each
application. Please ask the VEGA agency serving you.

8

.2 Remove interferences

T

he operator of the system is responsible for taking suitable measures

to rectify faults.

VEGAWELL

52

offers maximum reliability. Nevertheless, faults can

occur during operation. These may be caused by the following, e.g.:

l

S

ensor

l

P

rocess

l

V

oltage supply

l

S

ignal processing

T

he first measures to be taken are to check the output signals as well

as to evaluate the error messages via the indicating and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
and the faults rectified this way.

S

hould these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.

T

he hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the
E

nglish language. The service is free of charge, only the standard

telephone costs will be charged.

C

onnect a handheld multimeter in the suitable measuring range

according to the wiring plan.

Maintenance

Cleaning

Reaction when malfunc-
tions occur

Failure reasons

Fault rectification

24

hour service hotline

Checking the 4 … 20 mA
signal

26

VEGAWELL

52 • 4 … 20

mA/HART Pt

8 M

aintenance and fault rectification

35402

-EN

-111021