The units % and mA are not available in multidrop operation because
in this case the loop current is fixed.
Adjustment range: mbar, bar, PSI, hPa, kPa, MPa, mmH2O, mH2O,
mHg, mm, cm, m, in, ft, %, °C, °F, K, V, mA, Ohm, USER
DurcBy activating the unit locking, the set indication unit is locked
against changes by the sensors, the display shows the sign "GESP/
LoC". Hence it is possible to adjust for the VEGADIS 62 another
indicating unit than the sensor unit, e.g. %. It will also not be
overwritten in case of a restart of the sensor. Adjustment changes on
the sensor however are automatically converted. The unit locking
functions onyl if the units of measuring range and indication come from
the same unit group.
When connecting a transmitter and its configuration via HART with a
unit from another unit group, then the unit locking will be deactivated.
For this purpose, the indicating unit is adjusted according to the
configured measuring range unit.
Adjustment range:
l
nGESP/UnLoC
l
GESP/LoC
Adjustment of the decimal point for the indication area of the digital
indication
Adjustment range: 0, 0.0, 0.00, 0.000
Activation of the digital filter 1. order.
Adjustment range: 0 … 10
Indication/Unit locking
Indication/Indication de-
cimal point
Indication/Digital filter