Adjustment of the measuring range final value of the connected
transmitter (for example 4 bar at a measuring range of -1 … 5 bar)
3)
The
measuring range endpoint is initially adopted by the sensor when
starting with connected sensor. Thereafter, the measuring range
endpoint of the sensor can be changed.
This is a max. adjustment to which 100 % current output is assigned.
The value entered here does not change the measuring range
beginning point.
If the unit is set to "USER", then this menu item is used for free scaling
of the indication.
Adjustment range: -9999 … 99999
Adjustment of the decimal point for the measuring range of the
connected transmitter
4)
If the unit is set to "USER", then this menu item is used for free scaling
of the indication.
Adjustment range: 0, 0.0, 0.00, 0.000
In this menu item, the actual measured value is accepted as span
setting for the sensor
5)
This is a span adjustment to which 100 % of the current output are
assigned. The value accepted here, does not change the zero point.
3)
Is not available with HART multidrop.
4)
Is not available with HART multidrop.
5)
Is not available with HART multidrop.