VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Profibus PA User Manual
Page 43
43
6 Set up with the indicating and adjustment module
VEGAPULS 61 • Profibus PA
36501-EN-121011
ing the product level. These settings can be made ahead of time
without the instrument having to be installed.
Proceed as follows:
1. Select the menu item "Setup" with [->] and confirm with [OK].
Now select with [->] the menu item "Min. adjustment" and confirm
with [OK].
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4. Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5. Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Proceed as follows:
1. Select with [->] the menu item max. adjustment and confirm with
[OK].
2. Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
Setup/Min. adjustment
Setup/Max. adjustment